Beijing GFUVE Instrument Transformer Manufacturer Co.,Ltd.

Beijing GFUVE Instrument Transformer Manufacturer Co.,Ltd. an exclusive current transformer, split core current transformer, current clamp & voltage transformer manufacturer.

Manufacturer from China
Active Member
8 Years
Home / Products / Primary Injection Test Equipment /

Large Current 1000A Primary Injection Test Equipment CT PT Analyzer 5KVA Capacity

Contact Now
Beijing GFUVE Instrument Transformer Manufacturer Co.,Ltd.
City:beijing
Province/State:beijing
Country/Region:china
Contact Person:Andy
Contact Now

Large Current 1000A Primary Injection Test Equipment CT PT Analyzer 5KVA Capacity

Ask Latest Price
Video Channel
Brand Name :GFUVE
Model Number :TEST-901
Certification :CE ISO
Place of Origin :CHINA
MOQ :1 Set
Payment Terms :Western Union, T/T, L/C, MoneyGram
Supply Ability :1000Sets/Month
Delivery Time :7 days
Packaging Details :Standard export case
Name :CT PT Ana;yzer
Accuracy :Accuracy
Current Output (AC) :1000A·5V or 500A·10V
Capacity :5KVA
Range :0-1100A
Resolution :0.1A
more
Contact Now

Add to Cart

Find Similar Videos
View Product Description

TEST-901 Large Current 1000A Primary Current Injection Test Set

TEST-901 primary current injection test set adopts ARM Chip to control its output process and large capacity of toroidal transformers. It is equipped with LCD display and current meter; it can show primary current value, second current value, turn ratio and the action time. Packing is used as aluminum alloy body with PC panel. TEST-901 is mainly applied to CT turn ratio testing in the power system and contact resistance test which need large current.

High-current generator is a necessary equipment in all walks of life in electrical commissioning needs

large current place, used in power plants, substations, electrical manufacturers and scientific research,

laboratory and other units, belonging to short-term or intermittent working system, It has a small size, light

weight, good performance, easy to use and maintenance features.

PARAMETERS

Electrical parameters 
Accuracy ±0.5%
Power Supply(AC) 220V±10%·25A, 50Hz/60Hz or
110V±10%·50A, 50Hz/60Hz
Current Output (AC) 1000A·5V or 500A·10V
Capacity 5KVA
The current output waveform distortion ≤5%
Dual protection overload electronic protection and software protection
Primary current 
Range 0-1100A
Resolution 0.1A
Accuracy <0.5%
Secondary measurement 
Range 0-6A
Resolution 0.001A
Accuracy <0.5%
Current duration 
1000A range 1000A 2-3minutes
500A 3-6minutes
500A range 500A 2-3minutes
With timer
Range 0.0001~999.99S
Resolution 0.001S
Accuracy <0.5%±5 words
Mechanical parameters 
Dimensions (W×D×H) (mm) 430×260×260
Weight(kg) 25
Environmental conditions 
Temperature -10°C to 40°C
Relative humidity ≤80%

PHOTO

Large Current 1000A Primary Injection Test Equipment CT PT Analyzer 5KVA Capacity

Inquiry Cart 0