0.1A Resolution Primary Current Injection Test Set Overload Electronic Protection

Ask Latest Price
Video Channel
Brand Name :GFUVE
Model Number :TEST-901
Place of Origin :China
MOQ :1
Payment Terms :T/T, Western Union
Supply Ability :5000
Delivery Time :1-2Week
Packaging Details :Standard Wooden Case
Accuracy :±0.5%
Power Supply(AC) :220V±10%·25A, 50Hz/60Hz or 110V±10%·50A, 50Hz/60Hz
Current Output (AC) :1000A·5V or 500A·10V
Capacity :5KVA
The current output waveform distortion :≤5%
Dual protection :overload electronic protection and software protection
Range :0-1100A
Resolution :0.1A
Secondary measurement  :0-6A
Usage :Auto Testing Machine,Universal Testing Machine,Strength Testing Machine,Primary Current Injection Source,Primary Current Injection Test Set
Working environment :Temperature -10~40
more
Contact Now

Add to Cart

Find Similar Videos
View Product Description

Primary Current Injection Test Set TEST-901

TEST-901 primary current injection test set adopts ARM Chip to control its output process and large capacity of toroidal transformers. It is equipped with LCD display and current meter; it can show primary current value, second current value, turn ratio and the action time. Packing is used as aluminum alloy body with PC panel. TEST-901 is mainly applied to CT turn ratio testing in the power system and contact resistance test which need large current.

Electrical parameters 
Accuracy ±0.5%
Power Supply(AC) 220V±10%·25A, 50Hz/60Hz or
110V±10%·50A, 50Hz/60Hz
Current Output (AC) 1000A·5V or 500A·10V
Capacity 5KVA
The current output waveform distortion ≤5%
Dual protection overload electronic protection and software protection
Primary current 
Range 0-1100A
Resolution 0.1A
Accuracy <0.5%
Secondary measurement 
Range 0-6A
Resolution 0.001A
Accuracy <0.5%
Current duration 
1000A range 1000A 2-3minutes
500A 3-6minutes
500A range 500A 2-3minutes
With timer
Range 0.0001~999.99S
Resolution 0.001S
Accuracy <0.5%±5 words
Mechanical parameters 
Dimensions (W×D×H) (mm) 430×260×260
Weight(kg) 25
Environmental conditions 
Temperature -10°C to 40°C
Relative humidity ≤80%

Inquiry Cart 0