Beijing GFUVE Instrument Transformer Manufacturer Co.,Ltd.

Beijing GFUVE Instrument Transformer Manufacturer Co.,Ltd. an exclusive current transformer, split core current transformer, current clamp & voltage transformer manufacturer.

Manufacturer from China
Active Member
8 Years
Home / Products / Portable Meter Test Equipment /

LCD 25VA RS232 TFT 500V Energy Meter Testing Equipment

Contact Now
Beijing GFUVE Instrument Transformer Manufacturer Co.,Ltd.
City:beijing
Province/State:beijing
Country/Region:china
Contact Person:Andy
Contact Now

LCD 25VA RS232 TFT 500V Energy Meter Testing Equipment

Ask Latest Price
Video Channel
Brand Name :GFUVE
Model Number :GF302D1 20A500V
Certification :CNAS , CE
Place of Origin :BEIJING CHINA
MOQ :1set
Payment Terms :L/C, D/A, D/P, T/T, Western Union, MoneyGram
Supply Ability :200sets/month
Delivery Time :7-10days
Packaging Details :standard export wooden box
NAMES :Three phase phantom load of testing energy meter
Application :energy meter error calibrator
Current Range :0-500V
LCD :7 inch color touch TFT
Energy Pulse :0-999999999
Color :Yellow
Usage :in the Laboratory
more
Contact Now

Add to Cart

Find Similar Videos
View Product Description

Laboratory Three phase phantom load of testing energy meter for portable meter test equipment

This 3 phase phantom load is used for energising either CT or Direct connected Energy meters during commissioning or routine testing. The GF302D1 can deliver over 50VA per phase at 100Amps / 0.5V. "Variacs" are used to adjust the current injection level from zero to full scale. Each phase has a dedicated display showing the voltage and current value.
The phantom loading is used for examining the current rating ability of the energy meter. The actual loading arrangement will waste a lot of power. The phantom loading consumes very less power as compared to real loading, and because of this reason, it is used for testing the meter.
Three Phase Voltage And Current Phantom Load GF302D1 - Beijing GFUVE Electronics Co. Ltd. Suited to heavy duty workshop testing of meters up to 150A or 200A, this Model is conveniently housed in two separate voltage and current units. Voltage unit: The unit is powered from a 3 phase 4 wire 220/380V supply.
We hold expertise in developing a wide range of exemplary Three Phase Test Benches. offered range comprises Three Phase Phantom Load Test Bench and Three Phase Meter Test Bench. offered products are manufactured by making use of supreme quality required basic material, in complete adherence with the defined parameters of the industry.

FEATURES

  • To set up and take the load regulation of voltage, current, phase angle, frequency and power factor, also can be used as AC current source, AC voltage source or power source.
  • To set 2-128 times of the amplitude and phase harmonics, and it can be added to the base wave in every harmonic output.
  • Frequency value is adjustable (AB and phase C).
  • Voltage, current output a wide range, big power, high stability, waveform distortion degree is small.
  • Strong with load ability, but it can take capacitive, sensibility, resistance of composite type load or load and load regulation is higher than 0.01%.
  • To apply the 32 bit MPU + DSP + FPGA, powerful flexible.
  • To use hardware PID, fast response, the change of load will not cause output volatility.
  • Industrial frequency waves as high as 50000 points a week of the wave kneading, signal output without filter, precise output waveform, the harmonic output precision, harmonic distortion degree is small.
  • Range switching automatically
  • To use software calibration, simple operation, stable and reliable.
  • To have big screen, 320 x 240 LCD display, Chinese or English interface, operating simply.
  • To have perfect over-current, over-voltage, heat, a shorts-and-opens, overload protection, failure detection automatically.
  • With RS232 interface, and PC connection
  • To take place machine software, it can be output through the PC software program.

PARAMETERS

Electrical parameters 
Accuracy class 0.05%, 0.1%
Power supply Single phase AC 85V-265V, 50/60 Hz
AC Voltage output 
Range (U1, U2, U3 phase) 57.7V/100V/220V/380V, switch automatically (max 420V)
Adjustment resolution 0.01%, 0.1%, 1%, 10%,
Accuracy 0.05% RG
Stability 0.005% RG/1min
Distortion degree better than 0.1% (not capacitive load)
Load Capacity 25VA
Full load regulation rate Less than 0.01% RG
Full load regulation time Less than 1mS
Temperature drift 8 PPM / °C
Long-term stability 60 PPM/year
AC Current output 
Range (I1, I2, I3 phase) 0.1/0.25A/0.5A/1A/5A/10A/20A, switch automatically
Adjustment resolution 0.01%, 0.1%, 1%, 10%,
Accuracy 0.05% RG
Stability 0.005% RG/1min
Distortion degree better than 0.1% (not capacitive load)
Load capacity 25VA
Full load regulation rate Less than 0.01% RG
Full load regulation time Less than 1mS
Temperature drift 8 PPM/°C
Long-term stability 60 PPM/year
Power output 
Active power accuracy 0.05%
Reactive power accuracy 0.1%
Stability 0.005% RG/1min
Phase 
Range 0°-359.99°
Adjustment resolution 0.01°, 0.1°, 1°, 10°
Accuracy 0.03°
Power factor  
Adjusting range -1 to 0 to +1
Resolution 0.0001
Accuracy 0.0005
Frequency 
Range 40-65Hz or 40-400Hz (option)
Adjustment resolution 0.001Hz, 0.01Hz, 0.1Hz, 1Hz
Accuracy 0.002Hz
Temperature drift 0.5PPM/°C
Long-term stability 4 PPM/year
Harmonic 
Harmonic times 2-128
Adjustment resolution 0.1% (compared with fundamental wave)
Harmonic content (compared with fundamental wave)
Voltage ≤40%
Current ≤40%
Phase 0°-360°
Capacitive load capacity 
0 - 280 V 1uF
280 - 420 V 0.6uF
Mechanical parameters 
Dimensions (W×D×H) (mm) 450x380x160
Weight (kg) 18

LCD 25VA RS232 TFT 500V Energy Meter Testing Equipment