Beijing GFUVE Instrument Transformer Manufacturer Co.,Ltd.

Beijing GFUVE Instrument Transformer Manufacturer Co.,Ltd. an exclusive current transformer, split core current transformer, current clamp & voltage transformer manufacturer.

Manufacturer from China
Active Member
8 Years
Home / Products / CT PT Analyzer /

GF106 CT PT Analyzer Ct Pt Testing Equipment Type Printer Portable Accuracy 0.05%

Contact Now
Beijing GFUVE Instrument Transformer Manufacturer Co.,Ltd.
City:beijing
Province/State:beijing
Country/Region:china
Contact Person:Andy
Contact Now

GF106 CT PT Analyzer Ct Pt Testing Equipment Type Printer Portable Accuracy 0.05%

Ask Latest Price
Video Channel
Brand Name :GFUVE
Model Number :GF106
Certification :CE
Place of Origin :China
MOQ :1SET
Payment Terms :T/T, MoneyGram, Western Union
Supply Ability :100set/month
Packaging Details :Wooden box
Accuracy :0.05%, 0.1%
Power supply :AC 220V±10% or AC 110V±10%, 50/60Hz
Automatic frequency variation range :0.1-60Hz
CT/PT phase error measurement :Resolution 0.01min
CT ratio error measurement :Range 1-30000
PT ratio error measurement :Range 1-10000
more
Contact Now

Add to Cart

Find Similar Videos
1000A 2500V Automatic Portable CT PT Analyzer For Ratio & Phase Error Testing 03:29
1000A 2500V Automatic Portable CT PT Analyzer For Ratio & Phase Error Testing
High Precision Portable CT PT Analyzer 0.02% / 0.05% Ratio Error With Printer 00:28
High Precision Portable CT PT Analyzer 0.02% / 0.05% Ratio Error With Printer
Current Injection CT PT Analyzer , Power Transformer Testing Equipment 5KVA 00:30
Current Injection CT PT Analyzer , Power Transformer Testing Equipment 5KVA
High Voltage Clamp Ammeter Recorder 2000A Wireless High Accuracy In 20KV Power Line 00:24
High Voltage Clamp Ammeter Recorder 2000A Wireless High Accuracy In 20KV Power Line
IP65 Waterproof Outdoor Split Core Current Transformer LZCK185-10 Single Phase 00:18
IP65 Waterproof Outdoor Split Core Current Transformer LZCK185-10 Single Phase
GFUVE S50 2MHz Bandwidth 500A Clamp On AC Current Probe With 52mm Jaw 00:18
GFUVE S50 2MHz Bandwidth 500A Clamp On AC Current Probe With 52mm Jaw
GFUVE P50 Low Voltage AC Current Probe 4-20mA Output Large Jaw Opening Easy Operation 00:17
GFUVE P50 Low Voltage AC Current Probe 4-20mA Output Large Jaw Opening Easy Operation
GFUVE Q8A1 High Precision Low Current Amp Probe Nickel Metal Core Accuracy Class 0.1 00:20
GFUVE Q8A1 High Precision Low Current Amp Probe Nickel Metal Core Accuracy Class 0.1
GFUVE Q8A2 10A High Sensitivity AC Current Clamp Probe Permalloy Core 8mm Jaw Opening 00:16
GFUVE Q8A2 10A High Sensitivity AC Current Clamp Probe Permalloy Core 8mm Jaw Opening
GFUVE Q13 Permalloy Oscilloscope Clamp on Amp AC Current Probe Compact Size For 10A Electrical clamp meter 00:17
GFUVE Q13 Permalloy Oscilloscope Clamp on Amp AC Current Probe Compact Size For 10A Electrical clamp meter
View Product Description

GF106 CT PT TESTER

FEATURES

  • Steady and transient state characteristic tests of various types of CT/PT
  • The use of advanced power technology, the test knee point reaches up to 40kV
  • No external other auxiliary equipment, stand-alone to complete all test items
  • CT test, easy to test, all the tests are using the same wire connection except the load test
  • It carries with thermal printer, so it can print test results on site
  • Parameters such as knee point current and voltage
  • Parameters such as 10% error curve, 5% error curve
  • The device can store 3000 groups of test data which would not be lost if the device is power off.
  • The data can be displayed and analyzed after the test, or transferred to PC through USB disk and produce a Word file report
  • Portability: weight < 12kg

FUNCTION

I. Current Transformer (CT) II. Voltage Transformer (PT)
1. Magnetization curve 1. Excitation characteristic test
2. Transformation ratio test 2. Transformation ratio test
3. Polarity 3. Polarity
4. 5% and 10% error curve 4. Ratio error, phases
5. Current Injecting 5. Degauss
6. Degauss 6. Calculation of knee point value
7. Ratio error, phases 7. Actual secondary load (burden), test (burden)
8. Automatic calculation of excitation knee point value 8. Resistance test
9. Actual secondary load test (burden) (load test) 
10. Resistance test 
11. Secondary winding time constant (Ts) 
12. Remanence coefficient (Kr) 
13. Transient dimensioning factor (Ktd) 
14. Peak instantaneous error (Er) 
15. Magnetizing inductance (LU) 

PARAMETERS

Electrical parameters
Accuracy 0.05%, 0.1%
Power supply AC 220V±10% or AC 110V±10%, 50/60Hz
Excitation output voltage 0-220Vrms
Excitation output current 0-5Arms (20A peak-value)
Automatic frequency variation range 0.1-60Hz
Equivalent excitation voltage ≤5000V
Accuracy ≤0.5% (0.2%RD+0.3%RG)
Secondary winding DC resistance measurement Range 0.1-300Ω
Accuracy ≤0.5% (0.2%RD+0.3%RG)
Secondary actual load measurement Range 5VA-1000VA
Accuracy ≤0.5% (0.2%RD+0.3%RG)±0.1VA
CT/PT phase error measurement Accuracy ±4min
Resolution 0.01min
CT ratio error measurement Range 1-30000
Accuracy ≤0.5%
PT ratio error measurement Range 1-10000
Accuracy ≤0.5%
Standards 
Reference standards GB1207-2006, GB1208-2006, GB16847-1997
IEC60044-1, IEC60044-6, IEC61869-2-2012
Safety standards GB 4793.1-2007
EMC EMC standard 89/336/EEC
FCC Subpart B of Part 15 Class A
IEC 1000-4-2/3/4/6
Mechanical parameters 
Overall dimension (L x W x H) (mm) 410 x 250 x 300
Weight (kg) ≤10
Environmental conditions 
Relative humidity 90RH%
Operating temperature -10°C to +40°C
Altitude ≤2000m

MAIN FUNCTIONS

The test items mainly include 
Steady Transient
excitation characteristic secondary winding time constant (Ts)
transformation ratio remanence coefficient (Kr)
polarity transient dimensioning factor (Ktd)
ratio error peak instantaneous error (Er)
phases magnetizing inductance (LU)
5% and 10% error curves other parameters
resistance 
secondary load 
Inquiry Cart 0