Beijing GFUVE Instrument Transformer Manufacturer Co.,Ltd.

Beijing GFUVE Instrument Transformer Manufacturer Co.,Ltd. an exclusive current transformer, split core current transformer, current clamp & voltage transformer manufacturer.

Manufacturer from China
Active Member
8 Years
Home / Products / CT PT Analyzer /

0.05% Accuracy CT PT Analyzer Ct Testing Equipment For Lab Testing GF1061

Contact Now
Beijing GFUVE Instrument Transformer Manufacturer Co.,Ltd.
City:beijing
Province/State:beijing
Country/Region:china
Contact Person:Andy
Contact Now

0.05% Accuracy CT PT Analyzer Ct Testing Equipment For Lab Testing GF1061

Ask Latest Price
Video Channel
Brand Name :GFUVE
Model Number :GF1061
Certification :CE,ISO9001,UL
Place of Origin :BEIJING,CHINA
MOQ :1 SET
Payment Terms :T/T, Western Union
Supply Ability :100+SET+per month
Delivery Time :5-8 work days
Packaging Details :standard wooden package
Power supply :AC 220V±10% or AC 120V±10%, 50/60Hz or Battery
Accuracy :0.05%
Output voltage :0-100Vrms
Output current :0-5Arms (20A peak-value)
Output power :0-400 VA (1500 VApeak)
Automatic frequency variation range :0.1-60Hz
Equivalent excitation voltage :≤5000V
Secondary winding DC resistance measurement :0.1-1000Ω
Secondary actual load measurement :5VA-1000VA
CT/PT phase error measurement :±1min (typical) / 3 min (guaranteed)
CT ratio error measurement :1-50000
PT ratio error measurement :1-10000
Warranty :36 months
more
Contact Now

Add to Cart

Find Similar Videos
View Product Description

PORTABLE PRECISION CURRENT TRANSFORMER TESTING CT PT ANALYZER

GF1061 portable CT PT analyzer is mainly used for field or lab testing, it can finish the measurements (M) and protection (P) class CT, PT and TYP class CT. Adopt 7 inch touch TFT LCD, self-equipped mini type printer supporting field printing; supporting to use USB flash disk to dump data. The CT PT Analyzer is the most complete and easy-to-use testing system for protection and metering CTs according to IEEE and IEC standards.

MAIN FUNCTIONS

I. Current Transformer (CT) II. Voltage Transformer (PT)
1. Magnetization curve 1. Excitation characteristic test
2. Transformation ratio test 2. Transformation ratio test
3. Polarity 3. Polarity
4. 5% and 10% error curve 4. Ratio error, phase error
5. Accuracy limiting factor (ALF) 5. Degauss
6. Degauss 6. Calculation of knee point value
7. Ratio error, phase error 7. Actual secondary load test (burden test)
8. Automatic calculation of excitation knee
point value
8. Resistance test
9. Actual secondary load test (burden test)
10. Resistance test 
11. Secondary time constant (Ts)
12. Remanence coefficient (Kr)
13. Transient dimensioning factor (Ktd)
14. Peak instantaneous error (Er)
15. Magnetizing inductance (LU)
16. Instruments security factor(FS)
17. Composite error

PARAMETERS

Electrical parameters
Accuracy 0.05%
Power supply AC 220V±10% or AC 120V±10%, 50/60Hz or Battery
Output voltage 0-100Vrms
Output current 0-5Arms (20A peak-value)
Output power 0-400 VA (1500 VApeak)
Automatic frequency variation range 0.1-60Hz
Equivalent excitation voltage ≤5000V
Accuracy ≤0.5%
Secondary winding DC resistance measurement Range 0.1-1000Ω
Accuracy ≤0.05%
Secondary actual load measurement Range 5VA-1000VA
Accuracy ≤0.5%±0.1VA
CT/PT phase error measurement Accuracy ±1min (typical) / 3 min (guaranteed)
Resolution 0.1min
CT ratio error measurement Range 1-50000
Accuracy ≤0.05%
PT ratio error measurement Range 1-10000
Accuracy ≤0.05%
Standards 
Reference standards GB1207-2006, GB1208-2006, GB16847-1997
IEC60044-1, IEC60044-6, IEC61869-2, ANSI/IEEE C57.13
Safety standards GB 4793.1-2007
EMC EMC standard 89/336/EEC
FCC Subpart B of Part 15 Class A
IEC 1000-4-2 /3 /4 /6
Mechanical parameters 
Overall dimension (L x W x H) (mm) 280 x 250 x 160
Weight (kg) ≤4
Environmental conditions 
Relative humidity Relative humidity 5%-95% not condensing
Operating temperature -10°C to +50°C
Storage temperature -20°C to +70°C
Altitude ≤1000m
Inquiry Cart 0