Beijing GFUVE Instrument Transformer Manufacturer Co.,Ltd.

Beijing GFUVE Instrument Transformer Manufacturer Co.,Ltd. an exclusive current transformer, split core current transformer, current clamp & voltage transformer manufacturer.

Manufacturer from China
Active Member
8 Years
Home / Products / Secondary Current Injection Test /

Three Phase Secondary Injection Test Kit Universal Protection Device High Precision

Contact Now
Beijing GFUVE Instrument Transformer Manufacturer Co.,Ltd.
City:beijing
Province/State:beijing
Country/Region:china
Contact Person:Andy
Contact Now

Three Phase Secondary Injection Test Kit Universal Protection Device High Precision

Ask Latest Price
Video Channel
Brand Name :GFUVE
Model Number :TEST-330
Certification :CE,CNAS
Place of Origin :China
MOQ :1SET
Payment Terms :T/T, Western Union, MoneyGram
Supply Ability :100set/month
Packaging Details :Wooden box
Accuracy :0.2%
AC current output  :3 x 0-30A
AC voltage output  :5 x 0-130V
model :TEST-330
name :Secondary Injection Test Kit
feature :High Precision
more
Contact Now

Add to Cart

Find Similar Videos
View Product Description

TEST-330 THREE PHASE RELAY PROTECTION MICROCOMPUTER TEST SYSTEM

Test-330 is a three phase current output and five phase voltage output relay tester with embedded host machine equipped with Complex Programmable Logic Device.

FEATURES

  • Three phase current output
  • Five phase voltage output
  • Accuracy class 0.2%
  • Embedded host machine equipped with Complex Programmable Logic Device (CPLD)
  • Eight-path synchronous D/A output in a single machine
  • High-accuracy linear power amplifier
  • Host machine integrated single cabinet structure with big LCD screen and complete interface has obtained appearance patent
  • Intelligent self-protection function
  • Plentiful Binary and powerful software function
  • Easily complete the ABB, Siemens, AREVA, Schneider, GE, SEL, VAMP, Toshiba, NR, Sifang and other foreign manufacturers of protective device test
  • Synchronous output of five-phase voltage and three-phase current, Max AC current output is 90A, Max AC voltage output is 260V

OVERVIEW

  • Three phase current output
  • Five phase voltage output
  • Accuracy class 0.2%

TEST ITEM

  • U/I test
  • DC test
  • Impedance characteristics
  • Power direction test
  • I-T test
  • Differential relay
  • Harmonic test
  • Differential protection
  • Distance protection
  • Zero sequence protection
  • Setting group test
  • State sequence
  • Synchronization test
  • Special test
  • Oscillation test
  • Metering instrument
  • Hardware checkout
  • Low Voltage protection
  • Fault Recurrence

PARAMETERS

Electrical parameters
Power voltage AC220V±10% or AC110V±10%, 50/60Hz±10%
Time measurement 0.1ms-999999.999s
AC current output 
Phase current output (effective value) 3 x 0-30A
Maximum power output 260VA/phase
Maximum parallel current output (effective value) 0-90A
Long-term allowable working value of phase current
(effective value)
>10A
Allowable working time of maximum current >11s
Accuracy class <±0.2%
AC voltage output 
Phase voltage output (effective value) 5 x 0-130V
Line voltage output (effective value) 0-260V
Maximum power output 70VA/phase
Accuracy class <±0.2%
DC current output 
Output range -10 to 10A or 3 x 0 to ±10A
Maximum power output 200VA
Accuracy class <±0.2%
DC voltage output 
Output range 0-300V or 5 x 0 to ±130V
Maximum output power 130VA
Accuracy class <±0.2%
Binary input 
Idle contact 1-20mA, 24V (DC)
Electric potential contact 250V/0.5A (DC)
Binary output 
Idle contact 250V/0.5A (DC)
Rated output 
Frequency error <±0.01Hz
Phase error <±0.2°
Waveform distortion <±0.3% (fundamental wave)
Time error <40µs
Output frequency 0-1050Hz
Superposed harmonic wave 0-21times
Mechanical parameters 
Dimensions (L×W×H) (mm) 360x195x375
Weight (kg) 16.6
Environmental conditions
Use range 0°C to 45°C
Storage range -25°C to 70°C
Inquiry Cart 0