Beijing GFUVE Instrument Transformer Manufacturer Co.,Ltd.

Beijing GFUVE Instrument Transformer Manufacturer Co.,Ltd. an exclusive current transformer, split core current transformer, current clamp & voltage transformer manufacturer.

Manufacturer from China
Active Member
8 Years
Home / Products / Portable Meter Test Equipment /

Lab Portable Meter Test Equipment High Accuracy With Automatic Testing PC Software

Contact Now
Beijing GFUVE Instrument Transformer Manufacturer Co.,Ltd.
City:beijing
Province/State:beijing
Country/Region:china
Contact Person:Andy
Contact Now

Lab Portable Meter Test Equipment High Accuracy With Automatic Testing PC Software

Ask Latest Price
Video Channel
Brand Name :GFUVE
Model Number :GF302D-20A
Certification :CE, ISO9001
Place of Origin :BEIJING CHINA
MOQ :1SET
Payment Terms :L/C, D/A, D/P, T/T, Western Union, MoneyGram
Supply Ability :200sets/month
Delivery Time :2weeks
Packaging Details :Standard Export Wooden Box
Name :watthour meter test equipment
Application :electric meter & power meter test
Usage :lab and factory
Accuracy :0.05%
Function :0.05% voltage source & current source
Current Output :0-120A
Voltage Output :0-500V
Frequency :40-70Hz
Phase Angle :0-360.00
Harmonics :2-51st
more
Contact Now

Add to Cart

Find Similar Videos
View Product Description

Three Phase Portable watthour meter test equipment with Automatic testing PC software

The GF302D is a powerful and Three Phase Portable watthour meter test equipment . All test values are generated absolutely synthetically with a high degree of accuracy, low phase shift and stability. The test eqipment is available in 12 A, 24A or 120 A.
The GF302D Three Phase Portable watthour meter test equipment is a lightweight and portable three phase current and voltage source based on newest technology and serves for solving this problem by simulating the required load conditions. Operation is performed by integrated 7“ touch screen or via keyboards.

Watthour meter testing. With the testing requirements of today’s advanced systems, it is essential to take advantage of the new technological features of the Multi-Amp watthour meter test equipment. No matter what size your operation, you will find that Megger offers a range of instruments for watthour meter testing from portable meter testers.

APPLICATION

It is suitable for power department, measuring department, quality control department, research units, and institutions of higher learning, and electric energy meter, power distribution terminals, power supply management, load control, power quality, reactive power compensation device and the production of enterprise etc.

FEATURES

  • Min current output 1mA
  • Predefined multiple load points
  • Reference meter and power source integration
  • User friendly menu guided operation
  • Easy verification and analysis of meter installations
  • Automatic operation without need of an external PC
  • Generation of harmonics in current and voltage up to the 51th
  • Verification of the load conditions on metering installation
  • Verification of the energy registration
  • Automatic testing mechanical meter and electronic meter error
  • Voltage, current, frequency, phase angle, power factor, harmonics can be regulated
  • 1P2W, 1P3W, 3P3W, 3P4W can be set
  • 4 quadrant measurement
  • Vector diagram display and phase sequence indication on integrated colored screen
  • Especially configured USB stick for storage of customer data and measurement results

PARAMETERS

Electrical parameters 
Accuracy 0.02%, 0.05%, 0.1%
Power Supply Single phase AC 85-265V, frequency 50/60Hz.
AC Voltage Output 
Range(U1,U2,U3) 57.7V, 100V, 220V, 380V
or 69.3V, 120V, 240V, 480V( optional); max 500V
Adjustment range (0-120)%RG(1)
Adjustment fineness 0.01%RG, 0.1%RG, 1%RG, 10%RG as optional.
Stability 0.01%/120s
Distortion 0.2% (Non-capacitive load)
Output load each phase 25VA
Accuracy 0.05%RG or 0.02%RG
AC Current Output 
Range(I1,I2,I3) 200mA, 1A, 5A, 20A; max 25A
Adjustment range (0-120)%RG
Adjustment fineness 0.01%RG, 0.1%RG, 1%RG, 10%RG as optional.
Stability <0.01%/120s
Distortion ≤0.2% (Non-capacitive load)
Output load 25VA
Accuracy 0.05%RG or 0.02%RG
Power Output  
Active power output stability <0.01%RG/120s
Reactive power output stability <0.02%RG/120s
Active power measuring accuracy 0.05%RG or 0.02%RG
Reactive power measuring accuracy 0.1%RG
Phase Output  
Output adjustment range 0°-359.999°
Output adjustment fineness 10, 1, 0.1, 0.01 as optional.
Resolution 0.01°
Accuracy 0.02°
Power Factor 
Adjustment range -1 ~ 0 ~ 1
Resolution 0.0001
Measurement accuracy 0. 0005
Frequency Output  
Adjustment range 40Hz-70Hz
Output adjustment fineness 5Hz, 1Hz, 0.1Hz, 0.01Hz as optional.
Resolution 0.001Hz
Accuracy 0.002Hz
Voltage /Current/Harmonic Setting Output
Harmonic number 2-51times
Harmonic content 0-40%
Harmonic phase 0-359.99
Harmonic setting accuracy (10%±0.1%)RD(2)
Power Energy Measurement Error 
Active power energy 0.05%RG or 0.02%RG
Reactive power energy 0.1%RG
Power Pulse Output  
Power pulse type active pulse, reactive pulse
Active power pulse output 5V, 10mA
Power Pulse Input 
Energy pulse type support active and reactive pulse, the highest frequency power pulse input is 180K.
Communication Port
Communication Port RS232, USB2.0
Safety
Isolation protection IEC 61010-1:2001
Measurement Category 300 V CAT III, 600 V CAT II
Degree of protection IP20
Declaration of conformity CE certified
Mechanical parameters 
Dimensions (W×D×H) (mm) 445x460x158
Weight (kg) 18
(1) RG means range, the same as below;
(2) RD means the setted harmonic content, harmonic can be a single output, also multiple output.

Inquiry Cart 0