Add to Cart
T-212 Automatic Power Transformer Group Turns Ratio Tester With 58mm printer
In power transformer Finished product production process, before the new installation of the transformer in operation, according to the national ministry of preventive test procedures, require the operation of transformer turn ratio or voltage ratio test, to check the correctness of the transformer turn ratio tap-changer of transformer whether interturn short circuit transformer whether can run parallel.
T-203 automatic transformer turns ratio tester adopts three-phase power supply output voltage, the test speed Instrument to adopt advanced technology for A/D, wide range range; High speed single chip microcomputer as the core digital processor, the test fast; Chinese menu display, comprehensively improve the humanization and intelligent, instrument optional RS232C serial and USB come with computer on line, to realize the remote control of the instrument and intelligent analysis of the data A three phase transformation ratio test, the test speed High accuracy Perfect protection function.
Technical Data
Product Model | T-203 |
Rated working condition | Operating temperature: - 10℃ to 50℃; storage: - 20℃ to + 70℃. Relative humidity : 5 - 95%, without condensing. |
Input power | AC 220V/240V±10% AC, 50Hz/60Hz + 10% |
Test power | AC160V/10V |
data storage | 100 group |
Display precision | 5 Bits, resolution ratio: 0.0001 |
160V testing voltage | 0.9-500:0.1%±2words; 500-3000:0.2%±2words; 3000-10000:0.5%±2words; |
10V testing voltage | 0.9-200:0.3%±2words; |
LCD | 5.7″black and white LCD display (320 x 240 pixels) |
Communication | RS232 and USB communication interface |
Printer | internal installed 58mm wide thermal printer. |
DIMENSIONS | 415mm×320mm×168mm |
WEIGHT | 7kg |