Ask Latest Price
Video Channel
Brand Name :GFUVE
Model Number :GF303
Certification :CE,ISO9001:2008,IEC
Place of Origin :Beijing China
MOQ :1Set
Price :US$10000~US$12000/Set
Supply Ability :US$9000~US$11000/Set
Delivery Time :20days upon receipt of firm order
Packaging Details :Aluminium alloy box
GF303 :GF303 Program-controlled Three-phase Standard Power Source
Accuracy class :0.05% 0.1%
Power supply :Single phase AC 85V-265V
Phase range :0°-359.99°
Frequency range :40-65Hz or 40-400Hz (option)
Display :320 x 240 LCD display
Display language :English version
Current output :120A Max
more
Contact Now

Add to Cart

Find Similar Videos
View Product Description



GF303 Program-controlled Three-phase Standard Power Source with high accuracy class


(Accuracy class 0.05%/0.1%)


Application
GF303 Program-controlled Three-phase Standard Power Source is suitable for power department, measuring department, quality control department, research units, institutions of higher learning, electric energy meter, power distribution terminals, power supply management, load control, power quality, reactive power compensation device and the production of enterprise etc.

Features

1. To set up and take the load regulation of voltage, current, phase angle, frequency and power factor, also can be used as AC current source, AC voltage source or power source.

2. To set 2-128 times of the amplitude and phase harmonics, and it can be added to the base wave in every harmonic output.

3. Frequency value is adjustable (AB and phase C).

4. Voltage, current output a wide range, big power, high stability, waveform distortion degree is small.

5. Strong with load ability, but it can take capacitive, sensibility, resistance of composite type load or load and load regulation is higher than 0.01%.

6. To apply the 32 bit MPU + DSP + FPGA, powerful flexible.

7. To use hardware PID, fast response, the change of load will not cause output volatility.

8. Industrial frequency waves as high as 50000 points a week of the wave kneading, signal output without filter, precise output waveform, the harmonic output precision, harmonic distortion degree is small.

9. Range switching automatically

10. To use software calibration, simple operation, stable and reliable.

11. To have big screen, 320 x 240 LCD display, Chinese or English interface, operating simply.

12. To have perfect over-current, over-voltage, heat, a shorts-and-opens, overload protection, failure detection automatically.

13. With RS232 interface, and PC connection

14. To take place machine software, it can be output through the PC software program.

Electrical parameters  
Accuracy class 0.05%, 0.1%
Power supply Single phase AC 85V-265V, 50/60 Hz
AC Voltage output  
Range (U1, U2, U3 phase) 57.7V / 100V / 220V / 380V, switch automatically (max 420V)
Adjustment resolution 0.01%, 0.1%, 1%, 10%,
Accuracy 0.05% RG
Stability 0.005% RG / 1 min
Distortion degree better than 0.1% (not capacitive load)
Load Capacity 25VA
Full load regulation rate Less than 0.01% RG
Full load regulation time Less than 1mS
Temperature drift 8 PPM / °C
Long-term stability 60 PPM/year
AC Current output  
Range (I1, I2, I3 phase) 0.1/ 0.25A / 0.5A / 1A / 5A / 10A / 20A, switch automatically
Adjustment resolution 0.01%, 0.1%, 1%, 10%,
Accuracy 0.05% RG
Stability 0.005% RG/1min
Distortion degree better than 0.1% (not capacitive load)
Load capacity 25VA
Full load regulation rate Less than 0.01% RG
Full load regulation time Less than 1mS
Temperature drift 8 PPM/°C
Long-term stability 60 PPM/year
Power output  
Active power accuracy 0.05%
Reactive power accuracy 0.1%
Stability 0.005% RG / 1 min
Phase  
Range 0°-359.99°
Adjustment resolution 0.01°, 0.1°, 1°, 10°
Accuracy 0.03°
Power factor  
Adjusting range -1 to 0 to +1
Resolution 0.0001
Accuracy 0.0005
Frequency  
Range 40-65Hz or 40-400Hz (option)
Adjustment resolution 0.001Hz, 0.01Hz, 0.1Hz, 1Hz
Accuracy 0.002Hz
Temperature drift 0.5PPM/°C
Long-term stability 4 PPM/year
Harmonic  
Harmonic times 2-128
Adjustment resolution 0.1% (compared with fundamental wave)
Harmonic content (compared with fundamental wave)
Voltage ≤40%
Current ≤40%
Phase 0°-360°
Capacitive load capacity  
0 - 280 V 1uF
280 - 420 V 0.6uF
Mechanical parameters  
Dimensions (W×D×H) (mm) 450x380x160
Weight (kg) 18
Environmental conditions  
Working temperature 0°C to 40°C
Storage conditions -30°C to 60°C
Relative humidity ≤85%